| Rated voltage and insulation |
12 KV |
| Rated maximum current of the feeders |
1250A |
| Rated maximum current of the busbar |
2000A |
| Rated short-time current for 3 second |
25 KA |
| Rated short circuit breaking current(effective value) |
25 KA |
| Rated short circuit making current(peak value) |
62.5 KA |
| Power frequency withstand voltage(effective value) |
28 KV |
| Lighting impulse withstand voltage(peak value) |
75 KV |
| Dimension of panel : |
Width |
| |
Depth |
| |
Height |
|
630mm(approx)
1735mm(approx)
2450mm(max) |
| Weight of panel with breaker |
700-1000Kg. |