In Conformance with BS 6480, IEC 55 (Part I & Part II), VDE 0255 & IS 692.
TESTING ITEMS U °/U | TYPE 8.7/ 15 (17.5) KV |
---|---|
50 Hz Voltage test | 39 kV, 5min, no flashover, no strite |
Partial discharge test | 15 kV < 1pc |
Cyclic load test, 3 cycles | 3 cycles under 90-95°C, 22kV |
Impulses voltage test | 95kV no flashover, no strike |
15 min, 50 Hz voltage with standing test | 22kV, 15 min, no flashover,no strike |
Humidity test | No any flashover, tracking erosion or mechanical damage occur at 1000h, 11kV |
14.5/25 KV | 20.2/35 KV |
---|---|
65 kV, 5min, no flashover, no strite | 91 kV, 5min, no flashover, no strite |
25 kV < 1pc | 35 kV < 2pc |
3 cycles under 90-95°C, 36kV | 3 cycles under 90-95°C, 51.5 kV |
125kV no flashover, no strike | 194kV no flashover, no strike |
36kV, 15 min, no flashover,no strike | 51kV, 15 min, no flashover,no strike |
No any flashover, tracking erosion or mechanical damage occur at 1000h, 16kV | No any flashover, tracking erosion or mechanical damage occur at 1000h, 24kV |
CABLE CROSS SECTION (Sq. mm) | FOR 8.5 (15)kV 1 CORE INDOOR TERMINATION (Kit Code) | |
---|---|---|
25 - 50 | DCSI 15-1X1 | Enquire Now |
70 - 120 | DCSI 15-1X2 | Enquire Now |
150 - 240 | DCSI 15-1X3 | Enquire Now |
300 - 400 | DCSI 14-1X4 | Enquire Now |
CABLE CROSS SECTION (Sq. mm) | FOR 8.5 (15)kV 3 CORE INDOOR TERMINATION (Kit Code) | |
---|---|---|
25 - 50 | DCSI 15-3X1 | Enquire Now |
70 - 120 | DCSI 15-3X2 | Enquire Now |
150 - 240 | DCSI 15-3X3 | Enquire Now |
300 - 400 | DCSI 15-3X4 | Enquire Now |
CABLE CROSS SECTION (Sq. mm) | FOR 14.5 (25) kV 1 CORE INDOOR TERMINATION (Kit Code) | |
---|---|---|
50 - 95 | DCSI 25-1X1 | Enquire Now |
120 - 185 | DCSI 25-1X2 | Enquire Now |
240 - 400 | DCSI 25-1X3 | Enquire Now |
CABLE CROSS SECTION (Sq. mm) | FOR 14.5 (25) kV 3 CORE INDOOR TERMINATION (Kit Code) | |
---|---|---|
50 - 95 | DCSI 25-3X1 | Enquire Now |
120 - 185 | DCSI 25-3X2 | Enquire Now |
240 - 400 | DCSI 25-3X3 | Enquire Now |
CABLE CROSS SECTION (Sq. mm) | FOR 20.2 (35) kV 1 CORE INDOOR TERMINATION (Kit Code) | |
---|---|---|
50 - 95 | DCSI 35-1X1 | Enquire Now |
120 - 185 | DCSI 35-1X2 | Enquire Now |
240 - 400 | DCSI 35-1X3 | Enquire Now |
CABLE CROSS SECTION (Sq. mm) | FOR 20.2 (35) kV 3 CORE INDOOR TERMINATION (Kit Code) | |
---|---|---|
25 - 70 | DCSI 35-3X1 | Enquire Now |
95 - 185 | DCSI 35-3X2 | Enquire Now |
240 - 400 | DCSI 35-3X3 | Enquire Now |
Kindly provide your information, and our expert team will get in touch with you shortly.