Terminations

Cold Shrink Indoor Terminations upto 36 kV

Download Brochure Densons Cold Shrink Indoor Terminations upto 36 kV For XLPE Cable

"The term ’Cold Shrink’ is applied to materials, which are capable of shrinking without raising the material above the ambient temperature of its immediate surroundings. The Cold Shrink Accessories are supplied from the factory in a pre-expanded condition and placed on a removable core. Removing the core when properly positioned over the cables causes shrinking."

Enquire Now

Features

  • It does not require heating by flaming nor special tools. Pull out the plastic string from silicon rubber tube, the silicon rubber will tightly shrink on the need position.
  • Reliable, superior insulation & high-recovery elasticity; we have adopted special silicon rubber, which will keep its radial pressure permanently ensuring environmental & electrical protection.
  • Superior hermetic sealing; for cable splicing, we have adopted triple hermetic sealing technology & silicon rubber with hermetic & hydrophobic performance; there will be no serious fault due to environmental cause.
  • Easy/convenient installation : by enlarging the dimensions of stress-cone, large tolerance will be permitted & faults due to installation are reduced to a minimum.
  • Wide Usage : possessing a series of superior performance such as anti-pollution, long usage, hydrophobic, cold-withstanding etc. The Cold Shrink accessories can be widely used in various regions, especially suitable for high level region, cold weather region, high-humidity region, salt-fog region & high-polluted region etc.
Cold Shrink Indoor Terminations upto 36 kV

1.1 kV PVC/XLPE Termination

Specifications

TEST ITEMS OF COLD SHRINK INDOOR TERMINATIONS

TESTING ITEMS U °/U TYPE 8.7/ 15 (17.5) KV
50 Hz Voltage test 39 kV, 5min, no flashover, no strite
Partial discharge test 15 kV < 1pc
Cyclic load test, 3 cycles 3 cycles under 90-95°C, 22kV
Impulses voltage test 95kV no flashover, no strike
15 min, 50 Hz voltage with standing test 22kV, 15 min, no flashover,no strike
Humidity test No any flashover, tracking erosion or mechanical damage occur at 1000h, 11kV
14.5/25 KV 20.2/35 KV
65 kV, 5min, no flashover, no strite 91 kV, 5min, no flashover, no strite
25 kV < 1pc 35 kV < 2pc
3 cycles under 90-95°C, 36kV 3 cycles under 90-95°C, 51.5 kV
125kV no flashover, no strike 194kV no flashover, no strike
36kV, 15 min, no flashover,no strike 51kV, 15 min, no flashover,no strike
No any flashover, tracking erosion or mechanical damage occur at 1000h, 16kV No any flashover, tracking erosion or mechanical damage occur at 1000h, 24kV

Ordering Information

15 kV INDOOR TERMINATIONS

CABLE CROSS SECTION (Sq. mm) FOR 8.5 (15)kV 1 CORE INDOOR TERMINATION (Kit Code)  
25 - 50 DCSI 15-1X1 Enquire Now
70 - 120 DCSI 15-1X2 Enquire Now
150 - 240 DCSI 15-1X3 Enquire Now
300 - 400 DCSI 14-1X4 Enquire Now
CABLE CROSS SECTION (Sq. mm) FOR 8.5 (15)kV 3 CORE INDOOR TERMINATION (Kit Code)  
25 - 50 DCSI 15-3X1 Enquire Now
70 - 120 DCSI 15-3X2 Enquire Now
150 - 240 DCSI 15-3X3 Enquire Now
300 - 400 DCSI 15-3X4 Enquire Now

24 kV INDOOR TERMINATIONS

CABLE CROSS SECTION (Sq. mm) FOR 14.5 (25) kV 1 CORE INDOOR TERMINATION (Kit Code)  
50 - 95 DCSI 25-1X1 Enquire Now
120 - 185 DCSI 25-1X2 Enquire Now
240 - 400 DCSI 25-1X3 Enquire Now
CABLE CROSS SECTION (Sq. mm) FOR 14.5 (25) kV 3 CORE INDOOR TERMINATION (Kit Code)  
50 - 95 DCSI 25-3X1 Enquire Now
120 - 185 DCSI 25-3X2 Enquire Now
240 - 400 DCSI 25-3X3 Enquire Now

35 KV INDOOR TERMINATIONS

CABLE CROSS SECTION (Sq. mm) FOR 20.2 (35) kV 1 CORE INDOOR TERMINATION (Kit Code)  
50 - 95 DCSI 35-1X1 Enquire Now
120 - 185 DCSI 35-1X2 Enquire Now
240 - 400 DCSI 35-1X3 Enquire Now
CABLE CROSS SECTION (Sq. mm) FOR 20.2 (35) kV 3 CORE INDOOR TERMINATION (Kit Code)  
25 - 70 DCSI 35-3X1 Enquire Now
95 - 185 DCSI 35-3X2 Enquire Now
240 - 400 DCSI 35-3X3 Enquire Now
Send Message