Features
- Designed for medium voltage applications up to 36 KV
- Shaped components to meet a variety of configuration requriements
- Continuous operation temperature: -55° C to 120° C
- Used in proctecting cable and up to 36 KV against flashover or surges induce during working life in switch gear in and transformer boxes.
Technical Data
| Property |
Requirements |
Test Method |
| Tensile Strength |
8N/mm2 (min.) |
ASTM D412, ESI 09-13 |
| Elongation |
200% (min) |
ASTM D412, ESI 09-13 |
Heat Aging
(500 hrs. at 1200 C) |
|
|
| Tensile Strength |
7N/mm2 (min.) |
ASTM D412 |
| Elongation |
200% (min.) |
ASTM D412 |
Cold Temperature
Flex (-400 C) |
No cracking |
ASTM D2671 |
| Electrical |
|
|
Dielectric Strength
|
10 kV/mm (min.) |
ASTM D149, IEC 243 |
| Volume Resistivity |
1 x 1012 ohm-cm (min.) |
ASTM D257 |
| Track Resistance |
Non-Tracking |
ASTM D2303 |
| Chemical Resistance |
|
|
| Tensile Strength |
7N/mm2 (min.) |
ASTM D412 |
| Elongation |
200% (min.) |
ASTM D412 |
Ordering Information
| Code |
Expanded |
Recovered |
|
| Ø H (max.) |
Ø J(min.) |
Ø H (max.) |
Ø J(min.) |
| DRAB - 1 |
75 |
36 |
35 |
18 |
Enquiry |
| DRAB - 2 |
75 |
50 |
35 |
26 |
Enquiry |
| DRAB - 3 |
95 |
67 |
35 |
26 |
Enquiry |
|